■ Base accuracy: ±0.15 %
■ Span limits
– 0.3 to 60000 kPa; 1.2 inH2O to 8700 psi
– 0.3 to 3000 kPa abs; 2.25 mmHg to 435 psia
■ Reliable sensing system coupled with very latest
digital technologies
– provides large turn down ratio up to 20:1
■ Stainless steel housing
– optimized for rough environment
– extreme robust
■ Flexible configuration facilities
– local zero and span button
– local configuration with keys on LCD indicator
– remote configuration with hand terminal or PC based
software
■ Full compliance with PED Category III
Operative limits
Temperature limits °C (°F):
Ambient temperature limits (is the operating temperature)
40°C and +85°C (40°F and +185°F)
white oil filling: 6°C and +85°C (21°F and +185°F)
Lower limit for LCD indicator
and Viton gasket: 20°C (4°F)
Lower limit for perfluorelastomer gasket: 25°C/15°C (13°F/+5°F)
(ref. to section “Pressure Limits”)
Upper limit for perfluorelastomer gasket: +80°C (+176°F)
Upper limit for LCD indicator: +70°C (+158°F)
Note:
For Hazardous Atmosphere applications see the temperature range
specified on the certificate/approval relevant to the aimed type of
protection.
Process temperature limits
Lower limit
– 50°C (58°F); 20 C (4°F) for Viton gasket
25°C/15 °C (13 F/+5 °F) for perfluorelastomer gasket
(ref. to section “Pressure Limits”)
6°C (+21°F) for white oil filling
Upper limit
– +120°C (+250°F)
– +80°C (+176°F) for perfluorelastomer gasket
Storage temperature limits
Lower limit: 50°C (58°F), –40°C (40 °F) for LCD indicators
6°C (+21F) for white oil filling
Upper limit: +85°C (+185°F)
Pressure limits
Overpressure limits (without damage to the transmitter)
0 absolute to
– 1 MPa, 10 bar, 145 psi for sensor codes C, F
– 0.5 MPa, 5 bar, 72.5 psi for sensor code L
– 2 MPa, 20 bar, 290 psi für Sensorcode D
– 6 MPa, 60 bar, 870 psi for sensor code U
– 20 MPa, 200 bar, 2900 psi for sensor code R
– 90 MPa, 900 bar, 13050 psi for sensor code V
– 0.6 MPa abs, 6 bar abs, 87 psia for perfluoroelastomer gasket,
T ≥ 15 °C (+5 °F)
– 0.18 MPa abs, 1.8 bar abs, 26 psia for perfluoroelastomer gasket,
T ≥ 25 °C (13 °F)
Proof pressure
The transmitter can be exposed to line pressure for pressure test up
to:
refer to Overpressure limits