The OPTIFLEX 8200 is a 2-wire guided radar level transmitter based on the Time Domain Reflectometry (TDR) technology. It is designed for level and interface measurement under extreme conditions in the power, oil and gas industries. For high safety requirements in applications with dangerous media, the OPTIFLEX 8200 features a single or double ceramic process seal system. Various converter and electronic versions like a remote converter or a sensor extension facilitate the access to the device. The level transmitter has approvals for use in hazardous areas.
Specifications
Depending on selected device configuration
General information
Product type | Level transmitter |
Product family name | OPTIFLEX |
Product positioning | For liquids at high temperature and pressure |
Measurement variables | Distance, Level, Mass, Volume, Dielectric constant |
Measurement principle | Guided radar (TDR) |
Level measurement type | Continuous measurement |
Contact to measured medium | Yes |
Interface measurement | Yes |
Measured media | Liquids, Liquid/liquid interface |
Measuring range (liquids) | 0.6…60 m 1.97…196.85 ft |
Probe length units to display | m/ft |
Probe length | 0.6…60 m 1.97…196.85 ft |
Probe diameter |
|
Measuring point | Pressurised tank, Stilling well, Bypass |
Operating conditions
Process pressure | -1… 320 barg -14.5… 4641 psig |
Process temperature | -50…+315°C -58…+599°F |
Materials
Gaskets | Ethylene propylene diene monomer (EPDM), Fluoroelastomer rubber (FKM/FPM), Kalrez® 7075, Ceramic |
Wetted parts | Austenitic stainless steel (1.4404/316L), Austenitic alloy (2.4602/Alloy 22), Ceramic |
Process connections
Flange connections | EN (1092-1): DN25…200 ASME (B 16.5): 1…8″ JIS (B 2220): 40…100A |
Thread connections | Male: G1, G1½ 1 NPT, 1½ NPT |
Approvals/Standards
Ingress protection | IP66/68, NEMA4X/6 |
Certificates/Approvals Ex | ATEX, cQPSus, IECEx, NEPSI, INMETRO |
Certificates/Approvals Others | NACE |
Certificates/Approvals Safety | SIL 2 |
NAMUR compliance | NE 107, NE 21, NE 43, NE 53 |
Communication
Analogue outputs | 4…20 mA |
Discrete outputs | Relay |
Digital outputs | HART® |
Accuracy
Accuracy (liquids) | ±2 mm ±0,08 |