Vibronic Point level detection Liquiphant FTL85

  • Measuring principle

    Vibration Liquids

  • Characteristic / Application

    Coated point level switch for MIN and MAX safety applications up to SIL3,
    Dual Sealing/ Second line of defense,
    Modular housing concept

  • Specialities

    Outstanding features:
    – permanent LIVE signal monitors function safety
    – failsafe design and
    – high availability of the measuring values

  • Supply / Communication

    2-wire 4…20 mA

  • Ambient temperature

    -50°C…+70°C
    (-58°F…+160°F)

  • Process temperature

    –50°C…+150°C
    (–58°F…+300°F)

  • Process pressure / max. overpressure limit

    Vacuum…40 bar
    (580 psi)

  • Min. density of medium

    Density from 0.4 g/cm3
    (0.4 SGU)

  • Main wetted parts

    With high corrosion-resistant coating made of enamel, ECTFE and various PFA materials

  • Process connection

    Flange:
    DN25…DN100,
    ASME 1″…4″,
    JIS 10K…20K

  • Sensor length

    Extension pipe up to 3 m (9.8 ft)

  • Communication

    2-wire 4…20 mA

  • Certificates / Approvals

    ATEX, FM, CSA, CSA C/US, IEC Ex, NEPSI, EAC

  • Safety approvals

    Overfill protection WHG
    Leakage Detection
    SIL3

  • Options

    AlloyC Material
    PWIS free
    Pressure tight feed through
    Weather protection

  • Components

    Nivotester FTL825, Transmitter

Field of application
Liquiphant FTL85 is a coated point level switch for use in hazardous areas with all international certificates. FailSafe overfill protection in applications with functional safety up to SIL3 with one device. With high corrosion-resistant coating made of enamel, ECTFE and various PFA materials. Reliable measurement values, not affected by: changing media properties, flow, turbulences, gas bubbles, foam, vibrations or build-up.

Point level switch for liquids up to SIL3.Process connections: Threads and flangesTemperature: -50 to +150°C (-76 to +300°F)Pressure: -1 to +40bar (-14.5 to +580psi)Sensor length: Extension pipe up to 3m (9.8ft)Sensor material: Enamel, ECTFE and various PFA materialsInternational explosion protection certificates, overfill protection WHG, SIL

Benefits
Use in safety systems requiring functional safety to SIL3 in accordance with IEC 61508 Ed.2.0/ IEC 61511-1/ISA 84-1 and DIN EN ISO 13849Proof test: proof testing interval up to 12 years, Slave devices tested at the press of a button Permanent self-monitoring/internal redundancy4-20mA interface (acc. to NAMUR NE 06/NE 43): easy integration via the switching unit (Nivotester FailSafe FTL825) with a two-channel output (safety contacts) and locking function or direct integration into a safety PLCNo adjustment: quick, low-cost startupNo mechanically moving parts: no maintenance, no wear, long operating lifeMonitoring of fork for damage, corrosion, buildup and mechanical blocking