Capacitance Point level detection Liquicap FTI51

  • Measuring principle

    Capacitive Liquid

  • Characteristic / Application

    Capacitive rod probe

  • Specialities

    Interface detection
    Foam detection

  • Ambient temperature

    -50 °C … +70 °C
    (-58 °F … +158 °F)
    With separate housing:
    -50 °C … +120 °C
    (-58 °F … +248°F)

  • Process temperature

    -80 °C … +200 °C
    (-112 °F … +392 °F)

  • Process pressure / max. overpressure limit

    Vacuum … 100 bar
    (Vacuum … 1450 psi)

  • Main wetted parts

    Insulation material: PTFE, PFA
    316L

  • Process connection

    G 1/2 … 1 1/2
    NPT 1/2 … 1 1/2
    Flange from DN25…/ASME 1″…/JIS 10K…

  • Process connection hygienic

    Tri-Clamp ISO2852 gap free plated
    Dairy coupling
    Flush mount

  • Sensor length

    Total length of probe: max 6 m (20 ft)

  • Communication

    2- wire 19-253 VAC
    3-wire
    PFM
    Relay DPDT
    DC-PNP
    8/16 mA

  • Certificates / Approvals

    ATEX, FM, CSA, CSA C/US, IEC Ex, TIIS, INMETRO, NEPSI, EAC

  • Safety approvals

    Overfill prevention WHG
    SIL

  • Design approvals

    EN 10204-3.1
    NACE MR0175

  • Marine approval

    GL/ ABS/ DNV

  • Options

    Inactive length
    Fully isolated active build-up compensation
    Ground tube
    Separate housing

  • Components

    Transmitter
    PFM: FTC325, FTC625, FTC470Z, FTC471Z
    3-wire:
    FTC325

  • Application limits

    Notice the pressure and temperature derating.
    Notice for non conductive medium the DK.

Field of application
Liquicap FTI51 is a rod probe for point level detection of liquids that are highly viscous and tend to form build-up. Also used for detection of interface and foam of conductive liquids. Due to its active build-up compensation FTI51 offers maximum reliability and is suited for a wide range of applications thanks to international certificates. The parts in contact with the process are made of corrosion-resistant and FDA-listed materials – this guarantees a high safety standard.

For liquids that tend to form build-up. Interface detection of different liquids. Two-point control (pump control) with just one process connection. Foam detection of conductive liquids.
Process connections: Flanges, threads, special hygienic process connections
Temperature: -80 to +200°C (-112 to +392°F)
Pressure: Vacuum to +100bar (vacuum to +1,450psi)
Sensor length: 6m (20ft)
International explosion protection certificates, overfill prevention WHG, SIL, hygienic certificates, marine approval

Benefits
Cost savings thanks to easy and fast commissioning as calibration takes place at the press of a buttonReliable and safe measurement due to active build-up compensationReliable and universal application thanks to wide range of certificates and approvalsShort reaction timeMaterial in contact with the process made of corrosion-resistant and FDA-listed materialsTwo-stage overvoltage protectionNo need for recalibration after replacing electronics

Spread the love

Contact Us

    Please prove you are human by selecting the plane.