Measuring principle
Fieldbus indicators
-
Measuring principle
8 channel field indicator for fieldbuses
-
Function
Display values
Advanced diagnostic -
Display
High contrast backlit LCD with bargraph
TAG/unit -
Power Supply
Not defined
-
Input
Foundation Fieldbus protocol
PROFIBUS PA protocol -
Output
Not defined
-
Output
Not defined
-
Software functions
Listener Mode
On Foundation Fieldbus also function block connection:
Display transducer block
Advanced diagnostic block
2 x input selector
Arithmetic block
Integrator block
PID block -
Certificates
ATEX II2G Ex ia IIC T6
CSA General Purpose
CSA IS, NI I / 1+2/A-D
FM IS, NI I / 1+2/A-D
IECEx Ex ia IIC T6 Gb -
SIL
Not defined
-
Panel mounting
field
-
Measuring principle
Display
-
Function
Display values
Advanced diagnostic -
Certification
ATEX Ex ia
FM
CSA
IECEx Ex ia -
Input
Foundation Fieldbus protocol
PROFIBUS PA protocol -
Dimensions (wxhxd)
Field housing:
199 x 133 x 96 mm
(7.83 x 5.24″ x 3.78″) -
Software
Listener Mode
On Foundation Fieldbus also function block connection:
Display transducer block
Advanced diagnostic block
2 x input selector
Arithmetic block
Integrator block
PID block -
Operation
Foundation Fieldbus: via fieldbus
PROFIBUS PA: DTM and FieldCare or DIP-switches on the device
Write lock on hardware -
Display
High contrast backlit LCD with bargraph
TAG/unit -
Operating Voltage
9-32 V DC, polarity independent
Field of application
The 8 channel indicator shows measured and calculated values, and status information of the fieldbus users in a FOUNDATION Fieldbus™ or PROFIBUS® PA network. In the listener mode the device listens to the set fieldbus addresses and indicates their values. In addition, for FOUNDATION Fieldbus™ values available on the bus can be indicated via function block interconnection. A plain text field allows the display of the engineering unit or of the TAG. A bargraph is available for trend visualization.
Fieldbus indicator with 8 input channels and FOUNDATION Fieldbus™ or PROFIBUS® PA protocol for displaying process values and calculated values.
Benefits
Simple and standardized communication via fieldbus protocolListener mode for up to 8 analog channels or digital statusBrilliant, back lit LC display with bargraph, diagnostic symbols and clear text fieldNo external power supply requiredInternational approvals