Installing a conductivity measurement system may appear straightforward: connect the sensor, switch on the transmitter, configure several parameters, and check the reading.
However, experienced instrumentation engineers know that small mistakes during installation can lead to unstable measurements, incorrect temperature compensation, or mismatched 4–20 mA signals.
The Endress+Hauser Liquisys M CLM223 conductivity transmitter and Condumax CLS21 conductivity sensor are a typical example.
Although both devices are widely used in industrial liquid analysis, their wiring arrangements and configuration menus require careful attention.
This guide explains how to connect, configure, calibrate, and troubleshoot a CLM223 and CLS21 measurement system, following a practical commissioning sequence.
1. Understanding the CLM223 and CLS21 Measurement System
The Endress+Hauser CLM223 is a panel-mounted conductivity transmitter designed for industrial process monitoring.
It accepts conductive or inductive conductivity sensors, depending on the instrument version and configuration.
The Condumax CLS21 is a two-electrode conductive conductivity sensor suitable for applications involving moderate to relatively high conductivity levels.
Typical applications include:
Industrial process water monitoring
Cooling water systems
Wastewater treatment
Chemical processing
Water treatment equipment
General liquid conductivity monitoring
Main Technical Specifications
| Parameter | CLM223 / CLS21 |
|---|---|
| Transmitter | Endress+Hauser Liquisys M CLM223 |
| Sensor | Endress+Hauser Condumax CLS21 |
| Measurement principle | Conductive conductivity |
| Sensor design | Two-electrode |
| Typical cell constant | k = 1.0 cm-1 |
| CLS21 measurement range | 10 µS/cm to 20 mS/cm |
| Temperature measurement | Pt100, depending on sensor version |
| Analog output | 0/4–20 mA, depending on configuration |
| Transmitter installation | Panel mounting |
| CLM223 front protection | IP54 |
Important: Always check the exact transmitter order code, sensor version, and manufacturer documentation before installation. The available functions and electrical connections can vary between configurations.
2. Safety Checks Before Wiring
Before opening the transmitter or connecting the sensor, several safety precautions must be completed.
Disconnect the Power Supply
Ensure that the transmitter is completely disconnected from its electrical supply.
Verify the absence of voltage before touching the terminals.
Only qualified electrical or instrumentation personnel should perform installation and maintenance.
Verify the Supply Voltage
CLM223 transmitters are available in different supply configurations.
Check the nameplate to confirm whether the installed unit requires AC or low-voltage AC/DC power.
Never assume that all CLM223 transmitters operate from the same supply voltage.
Applying an incorrect voltage can permanently damage the electronics.
Check the Sensor and Cable
Before installation, inspect:
Sensor body and electrodes
Cable insulation
Connector condition
Cable shielding
Terminal identification
Moisture or corrosion inside connection points
Damaged insulation and moisture contamination can cause unstable conductivity readings.
3. CLM223 and CLS21 Wiring Connections
Correct wiring is one of the most important steps in the commissioning process.
The CLS21 operates according to the conductive measurement principle.
It must therefore be connected using the appropriate conductive sensor input arrangement.
Do not use wiring instructions intended for inductive conductivity sensors.
3.1 Conductivity Signal Connections
For the CLM223 conductive input, terminals 83 and 84 are associated with the conductivity measurement circuit.
These connections carry the sensor measurement signal.
However, the exact assignment of conductors must be verified using the applicable E+H wiring diagram for the sensor and cable assembly.
Do not identify the connections solely by assuming that one conductor represents an inner electrode and another represents an outer electrode.
3.2 Temperature Sensor Connections
When using a CLS21 fitted with a Pt100 temperature element, the CLM223 uses the designated temperature input terminals.
For the applicable three-wire configuration, terminals 11, 12, and 13 are used.
For the CYK71 cable arrangement shown in the manufacturer’s documentation, the temperature conductor colors are identified as:
| Terminal | Cable identification |
|---|---|
| 11 | Green (GN) |
| 12 | White (WH) |
| 13 | Yellow (YE) |
These conductor colors apply to the specified cable arrangement and should not be treated as universal for every sensor cable.
Check the actual cable documentation before making connections.
3.3 Cable Shielding
Conductivity measurements are sensitive to electrical interference, particularly when low conductivity values are being measured.
The sensor cable shield must be terminated according to the manufacturer’s conductive sensor wiring instructions.
For the applicable CLM223 conductive sensor arrangement, the shield connection is associated with the designated PE terminal.
The sensor cable shield, protective earth, and measurement signal conductors must not be confused with one another.
Avoid routing the conductivity sensor cable alongside:
Variable-frequency drive output cables
High-current motor power cables
Switching power conductors
Other strong sources of electromagnetic interference
Where possible, use separate cable routes and maintain sufficient separation from electrical power circuits.
3.4 Analog Output Connections
For the standard analog output arrangement:
| Terminal | Function |
|---|---|
| 31 (+) | Current output 1 positive |
| 32 (-) | Current output 1 negative |
| 33 (+) | Current output 2 positive, if fitted |
| 34 (-) | Current output 2 negative, if fitted |
Current output 1 is typically used to transmit conductivity measurements.
If the transmitter is equipped with a second analog output, it may be configured for temperature or another supported measured variable.
Check the specific hardware version before connecting the PLC or DCS.
Engineering tip: Never assume that an unused terminal is available for another purpose. Refer to the terminal diagram supplied with the actual transmitter.
4. Understanding the CLM223 Operating Keys
The CLM223 has several dedicated operating keys.
Understanding their functions helps prevent mistakes during configuration and calibration.
ENTER (E)
Used to:
Access configuration menus
Confirm parameter changes
Navigate between parameter fields
Save selected settings
PLUS (+) and MINUS (-)
Used to:
Select menu groups
Increase or decrease numerical values
Change configuration options
Navigate through available settings
Pressing PLUS and MINUS simultaneously provides the escape function.
Depending on the current menu level, this returns the operator to the preceding menu or measurement display.
CAL
The CAL key is used to access calibration functions.
REL and AUTO
These keys are associated with relay operation and automatic/manual operating modes where supported.
They are not substitutes for the normal configuration keys.
Accessing Configuration Mode
Start from the measurement display.
Press ENTER.
Enter access code 22 using PLUS and MINUS.
Press ENTER to confirm.
Select the required configuration group.
The transmitter will now allow the relevant parameters to be modified.
Important: Calibration and configuration use different entry keys. Do not confuse the CAL menu with the normal parameter setup menu.
5. Setup 1: Configuring Conductivity Measurement
The SETUP 1 function group defines the basic conductivity measurement parameters.
These settings should be checked before calibration or process commissioning.
A1: Measurement Mode
For the CLS21 conductive sensor, select the appropriate conductive conductivity measurement mode:
cond
The selected mode must match the sensor measurement principle and installed transmitter version.
Changing the measurement mode may affect other stored parameters, so record the existing settings before making modifications.
A4: Conductivity Display Unit
Select a suitable engineering unit according to the expected conductivity range.
Common options include:
µS/cm
mS/cm
For example, a process operating around 800 µS/cm is normally easier to monitor in µS/cm.
For a process around 12 mS/cm, using mS/cm is more convenient.
A5: Sensor Cell Constant
The cell constant is one of the most important parameters affecting measurement accuracy.
A CLS21 sensor commonly has a nominal cell constant of:
k = 1.000 cm-1
However, the actual cell constant may differ slightly from the nominal value.
For example, if the sensor calibration certificate specifies:
k = 0.998 cm-1
Enter 0.998 rather than automatically using 1.000.
An incorrect cell constant introduces a systematic error into the conductivity measurement.
Practical recommendation: Always obtain the actual sensor cell constant from the sensor certificate or a valid calibration result.
A6: Cable Resistance Compensation
For conductive conductivity measurement, cable resistance can influence accuracy.
This becomes especially relevant when long measurement cables are installed.
The CLM223 provides a cable resistance compensation setting for conductive sensors.
Cable resistance should be determined using the relevant cable specification or measurement procedure.
Do not automatically apply a resistance-per-metre value without confirming whether it represents an individual conductor, conductor pair, or the relevant measurement circuit.
A7: Measurement Damping
Measurement damping helps reduce fluctuations in the displayed conductivity value.
A setting of 1 corresponds to no averaging-related damping.
Higher settings provide a smoother displayed value but reduce the speed at which rapid process changes are reflected.
Use minimal damping for stable measurement conditions.
Increase damping only when necessary, particularly where the measured signal is naturally unstable.
Excessive damping can hide rapid process changes.
6. Setup 2: Temperature Compensation
Conductivity changes with temperature because the mobility of ions in a liquid is temperature-dependent.
Without appropriate temperature compensation, conductivity readings may vary significantly even when the liquid composition remains unchanged.
The CLM223 provides several temperature compensation methods.
B1: Temperature Sensor Type
Select the temperature sensor fitted to the actual CLS21 assembly.
For a CLS21 equipped with a Pt100 element:
B1 = Pt100
Other selections may be available in the transmitter, but the configured value must match the installed sensor.
An incorrect selection can cause temperature measurement errors and therefore incorrect temperature-compensated conductivity readings.
B2: Temperature Compensation Method
Common compensation modes include:
| Mode | Application |
|---|---|
| None | Uncompensated conductivity |
| Lin | Linear temperature compensation |
| NaCl | Sodium chloride-related compensation |
| Pure | Ultrapure water compensation |
| PureH | Ultrapure water compensation for the relevant acidic contamination model |
| Tab | User-defined compensation table, where supported |
For many ordinary industrial water applications, linear compensation is a practical starting point.
However, the correct compensation method depends on the actual chemical composition of the liquid.
B3: Temperature Coefficient
When linear compensation is selected, the transmitter uses a temperature coefficient.
An example setting is:
alpha = 2.10 %/K
This indicates the assumed relative conductivity change per degree of temperature change.
The coefficient of 2.10 %/K is not universally applicable.
Different process liquids can have significantly different temperature coefficients.
For accurate monitoring, verify the coefficient using process data, laboratory measurements, or a validated application reference.
B5 and B6: Temperature Adjustment
The temperature input can be checked against a reliable reference thermometer.
If the displayed temperature differs from the reference value, the relevant adjustment procedure can be used.
Before applying a temperature offset, check:
Sensor element selection
Temperature wiring
Cable condition
Sensor immersion
Reference thermometer accuracy
Do not use temperature offset adjustment to conceal an unresolved wiring problem.
B7: Reference Temperature
A commonly used reference temperature for conductivity reporting is:
25 °C
Ensure that the conductivity values expected by the laboratory, PLC, DCS, or quality control system use the same reference conditions.
Otherwise, two correct measurements may appear inconsistent because they are reported at different reference temperatures.
7. Configuring the 4–20 mA Output
The analog output allows the CLM223 to transmit conductivity measurements to a PLC, DCS, recorder, or other control system.
The relevant configuration is performed through the CURRENT OUTPUT function group.
O1: Select the Current Output
Select the required output channel.
For example:
Out1
If a second output is installed, configure it separately as required.
O3: Output Characteristic
For normal linear conductivity transmission, select:
Lin
O311: Current Range
Select:
4–20 mA
This is commonly used in industrial automation systems.
O312: Lower Range Value
Define the conductivity corresponding to 4 mA.
Example:
4 mA = 0 µS/cm
O313: Upper Range Value
Define the conductivity corresponding to 20 mA.
Example:
20 mA = 2000 µS/cm
Example: Checking the Analog Output
With the above configuration, the theoretical current output is:
I = 4 + 16 * (C - Cmin) / (Cmax - Cmin)
Where:
I = output current in mA
C = measured conductivity
Cmin = conductivity at 4 mA
Cmax = conductivity at 20 mA
For this example:
I = 4 + 16 * C / 2000
The expected current values are:
| Conductivity | Current Output |
|---|---|
| 0 µS/cm | 4 mA |
| 500 µS/cm | 8 mA |
| 1000 µS/cm | 12 mA |
| 1500 µS/cm | 16 mA |
| 2000 µS/cm | 20 mA |
These values assume normal measurement operation and a linear output without an active fault-current condition.
Common PLC/DCS Scaling Problem
Suppose the transmitter is configured for:
0–2000 µS/cm
But the PLC is configured for:
0–5000 µS/cm
The transmitter may display the correct conductivity while the PLC displays a completely different value.
This is not necessarily a sensor problem.
It is a scaling mismatch.
Always verify that the lower and upper range values match between the transmitter and the receiving control system.
Also confirm the analog input type, wiring arrangement, and actual measured loop current.
8. Sensor Calibration and Commissioning
The CLS21 sensor is supplied with a defined cell constant.
For a new sensor, the first step is to enter the correct value into the transmitter and verify the measurement.
Additional calibration may be required depending on process accuracy requirements, maintenance history, and quality procedures.
When Should Calibration Be Performed?
Calibration or verification is recommended when:
Installing a sensor with uncertain calibration history
Replacing an existing sensor
Investigating persistent measurement deviation
Performing scheduled calibration
Returning a cleaned sensor to a critical measurement service
Calibration Procedure
Prepare a suitable certified conductivity standard.
Check the standard’s reference temperature and stated conductivity.
Clean and rinse the sensor according to the manufacturer’s instructions.
Immerse the electrodes correctly in the calibration solution.
Remove trapped air bubbles.
Allow the sensor and solution temperature to stabilize.
Press the CAL key.
Enter access code 22 and confirm using CAL.
Select the appropriate conductive sensor calibration procedure.
Enter the required calibration solution parameters.
Follow the displayed instructions.
Review the resulting cell constant and calibration status.
Accept and save the result only when it is technically reasonable.
The detailed calibration fields may vary with the transmitter software version.
Important Calibration Precautions
Do not use a calibration solution that has been contaminated by previous measurements.
Do not return used solution to its original container.
Avoid direct sunlight or unnecessary heating of the calibration container.
Use a conductivity standard appropriate to the expected sensor range.
After calibration, verify the measured value and record the results.
Note: Air-set calibration procedures intended for inductive conductivity measurement must not be applied to the conductive CLS21 sensor.
9. Troubleshooting Common CLM223 and CLS21 Problems
Problem 1: Conductivity Reading Fluctuates Continuously
Possible causes include:
Poor electrical connections
Damaged sensor cable
Incorrect shielding
Moisture ingress
Electrical interference
Air bubbles around the electrodes
Unstable process conditions
Recommended troubleshooting:
Inspect the sensor and cable.
Check terminal tightness.
Verify shield termination against the wiring diagram.
Inspect the installation for electromagnetic interference.
Confirm proper sensor immersion.
Compare the measurement with a stable reference solution.
Do not assume that every fluctuating signal is caused by poor grounding.
Problem 2: Conductivity Reading Is Consistently Incorrect
Possible causes include:
Incorrect cell constant
Contaminated electrodes
Incorrect temperature compensation
Unsuitable calibration
Air bubbles
Actual changes in process composition
Start by checking the A5 cell constant and the temperature compensation settings.
Compare the transmitter reading with a suitable conductivity reference.
If contamination is suspected, clean the sensor using a method appropriate to the deposit and wetted materials.
Problem 3: Temperature Reading Is Incorrect
Check:
Pt100 selection in B1
Temperature wiring
Cable continuity
Loose or corroded connections
Sensor installation
Temperature offset settings
Compare the displayed temperature with a calibrated reference thermometer.
Correct electrical or installation problems before making software adjustments.
Problem 4: PLC Reading Does Not Match the Transmitter
Possible causes include:
Different analog scaling ranges
Incorrect PLC input configuration
Incorrect output channel selection
Wiring problems
Active fault-current output
Incorrect analog input interpretation
Use a suitable current measurement instrument to verify the actual output.
For example, if the transmitter is configured for 0–2000 µS/cm and displays 1000 µS/cm, the expected normal output is approximately 12 mA.
If the measured current is correct but the PLC value is wrong, investigate the PLC scaling.
If the measured current is incorrect, check the transmitter configuration and electrical connections.
Problem 5: Temperature Coefficient Cannot Be Changed
Check the compensation mode in B2.
The linear temperature coefficient setting applies when linear compensation is selected.
With certain other compensation modes, the transmitter uses an internal compensation characteristic rather than the manually entered linear coefficient.
This behavior does not necessarily indicate an instrument fault.
10. Cleaning and Maintaining the CLS21 Sensor
Electrode contamination is a common cause of conductivity measurement problems.
Different deposits require different cleaning methods.
Examples include:
| Contamination | General Maintenance Approach |
|---|---|
| Mineral scale | Use a manufacturer-approved cleaning method suitable for the deposit |
| Oil or grease | Use a compatible cleaning agent |
| Biological deposits | Use an appropriate approved cleaning procedure |
| Loose particles | Rinse carefully with clean water |
| Persistent deposits | Inspect and clean according to the sensor documentation |
Always consider the chemical compatibility of the sensor materials before using cleaning chemicals.
Never assume that acid cleaning is appropriate for every type of contamination.
After cleaning:
Rinse the sensor thoroughly.
Inspect the electrodes.
Check for mechanical damage.
Reinstall the sensor correctly.
Verify its response.
Perform calibration if required.
Regular inspection can prevent unexpected measurement errors and unnecessary sensor replacement.
11. Factory Reset and Parameter Backup
The CLM223 provides reset functions through the SERVICE menu.
The S9 function includes different reset options.
Typical selections include:
No: No reset
Sens: Reset relevant sensor calibration data
Facty: Restore the applicable factory settings
A factory reset can remove important user-defined parameters, although certain settings are excluded according to the manufacturer’s documentation.
Therefore, a reset should never be the first troubleshooting action.
Before performing any reset, record the existing configuration.
Recommended Parameter Backup Checklist
| Parameter | Information to Record |
|---|---|
| A1 | Measurement mode |
| A5 | Cell constant |
| A6 | Cable resistance |
| A7 | Measurement damping |
| B1 | Temperature sensor type |
| B2 | Compensation mode |
| B3 | Temperature coefficient |
| B7 | Reference temperature |
| O1/O2 | Output selection and measured variable |
| O311 | Current range |
| O312 | Lower output value |
| O313 | Upper output value |
Also document relevant alarm, relay, HOLD, and communication settings if the installed transmitter uses these functions.
Taking photographs of the configuration screens is a simple and effective way to preserve settings during maintenance.
12. Final Commissioning Checklist
Before handing over the conductivity measurement system, verify the following items.
| Inspection Item | Requirement |
|---|---|
| Transmitter supply | Matches the nameplate |
| Sensor compatibility | Confirmed for conductive measurement |
| Conductivity wiring | Verified against the applicable wiring diagram |
| Temperature wiring | Correct for the installed sensor |
| Cable shielding | Installed according to manufacturer instructions |
| Cell constant | Matches certificate or valid calibration |
| Temperature compensation | Appropriate for the liquid |
| Reference temperature | Matches process requirements |
| Analog output | Correct range and measured variable |
| PLC/DCS scaling | Matches transmitter configuration |
| Sensor installation | Proper immersion, no trapped air |
| Measurement verification | Acceptable against reference |
| Parameter backup | Completed |
| Alarm and control functions | Checked where applicable |
A properly commissioned measurement system should provide stable conductivity readings, reasonable temperature measurements, and consistent analog output signals.
Conclusion
Successful commissioning of an Endress+Hauser CLM223 and CLS21 conductivity measurement system depends on more than simply connecting the sensor and entering a few parameters.
The most important steps are:
Verify the sensor and transmitter compatibility.
Follow the correct conductive sensor wiring diagram.
Enter the actual sensor cell constant.
Configure the appropriate temperature compensation.
Match the analog output range with the PLC or DCS.
Verify the measurement using a suitable reference.
Record the final configuration before handing over the system.
When troubleshooting, always start with basic installation checks before replacing the transmitter or sensor.
A loose terminal, incorrect cell constant, unsuitable compensation coefficient, or PLC scaling mismatch can produce symptoms that look like serious instrument failure.
A systematic commissioning procedure saves maintenance time, reduces unnecessary replacement costs, and improves long-term measurement reliability.
For industrial instrumentation engineers, a few additional minutes spent verifying wiring, calibration parameters, and output signals can prevent hours of troubleshooting later.
Technical References
Endress+Hauser — Liquisys M CLM223/253 Operating Instructions, BA00193C
Endress+Hauser — Liquisys M CLM223/253 Technical Information, TI00193C
Endress+Hauser — Condumax CLS21 Sensor Technical Documentation
Endress+Hauser — Conductivity Measurement Cable and Installation Documentation
Technical note: This article provides general commissioning guidance. Exact connections, available menus, and calibration procedures depend on instrument hardware, software version, and sensor configuration. Always follow the official documentation supplied with the equipment.