This product is part of the Easy modicon M200 range, an offer of logic controllers for up to 168 I/O, 2 axis motion control. This logic controller provides 1 regular input, 4 fast inputs, 4 high speed inputs and 7 relay outputs, normally opened relay output. It is a Modicon logic controller with an input voltage of 24V DC, a discrete output voltage of 24V DC, 220V AC and an output current of 2A. Easy to maintain and update with its micro SD memory card.
Integrated connections are mini B USB 2.0, non isolated serial link 1 and RS485, non isolated serial link 2 and RS232/RS485, and isolated serial link 2 and RS485. It is a controller with an internal flash of 512byte and a micro SD card capacity of 32GB. It is an IP20 rated product. Its dimensions are 110mm (Width) x 70mm (Depth) x 90mm (Height). It weighs 0.359kg. Designed for textile, machine tool, packaging, material handling, pumping, hoisting, electronic assembly machines.
This product is certified by CE, CSA, IACS E10, RCM and CULus. It meets EN/IEC 61010-2-201 and EN/IEC 61131-2 standards. It supports DIN rail mount. Entry-level plc perfectly suited to meet specific needs of emerging markets at an affordable price without compromise. Best performance/price ratio solutions for your small automation systems requiring flexibility and simple motion.
Specifications
Main
Range of product |
Easy Modicon M200 |
Product or component type |
Logic controller |
[Us] rated supply voltage |
100…240 V AC |
Discrete I/O number |
16 |
Discrete input number |
I8: 1 regular input
I2…I5: 4 fast input
I0, I1, I6, I7: 4 high speed input |
Discrete output number |
7 relay |
Discrete input voltage |
24 V |
Discrete input voltage type |
DC |
Discrete input current |
7 mA for input |
Discrete input logic |
Sink or source (positive/negative) type 1 conforming to IEC 61131-2 |
Discrete output voltage |
24 V DC
220 V AC |
Discrete output current |
2 A |
Discrete output type |
Relay normally open |
Power consumption in VA |
51…63 VA at 100…240 V AC (with max I/O) |
Complementary
Maximum number of I/O expansion module |
4 with 64 discrete output(s) for transistor output
4 with 71 discrete output(s) for relay output |
Supply voltage limits |
85…264 V |
Network frequency |
50/60 Hz |
Inrush current |
50 A |
Voltage state 1 guaranteed |
>= 15 V for input |
Voltage state 0 guaranteed |
<= 5 V for input |
Input impedance |
3.3 kOhm for discrete input |
Response time |
10 ms turn-off, Q0…Q6 terminal(s) for relay output
10 ms turn-on, Q0…Q6 terminal(s) for relay output
5 µs turn-off, I0, I1, I6, I7 terminal(s) for high speed input
5 µs turn-on, I0, I1, I6, I7 terminal(s) for high speed input
100 µs turn-off, I2…I5 terminal(s) for fast input
35 µs turn-on, I2…I5 terminal(s) for fast input
100 µs turn-off, I8 terminal(s) for regular input
35 µs turn-on, I8 terminal(s) for regular input |
Configurable filtering time |
0 ms for input
3 ms for input
12 ms for input |
Output voltage limits |
30 V DC
250 V AC |
Maximum current per output common |
4 A at COM 0
4 A at COM 1 |
Electrical durability |
100000 cycles AC-12, 240 V, 480 VA, resistive
100000 cycles DC-12, 24 V, 48 W, resistive |
Switching frequency |
0.1 Hz with maximum load |
Mechanical durability |
20000000 cycles for relay output |
Minimum load |
10 mA at 5 V DC for relay output |
Memory capacity |
512 byte internal flash with 10000 instructions for backup of programs |
Data storage equipment |
32 GB micro SD card (optional) |
Battery type |
BR2032 Li-CFx (Lithium-Carbon Monofluoride), battery life: 5 year(s) |
Backup time |
3 years at 25 °C (by interruption of power supply) |
Execution time for 1 KInstruction |
0.3 ms for event and periodic task |
Execution time per instruction |
0.2 µs Boolean |
Exct time for event task |
60 µs response time |
Clock drift |
<= 90 s/month at 25 °C |
Regulation loop |
Adjustable PID regulator up to 14 simultaneous loops |
Control signal type |
Quadrature (x1, x2, x4) at 100 kHz for fast input (HSC mode)
Pulse/direction at 100 kHz for fast input (HSC mode)
Single phase at 100 kHz for fast input (HSC mode)
CW/CCW at 100 kHz for fast input (HSC mode) |
Counting input number |
4 fast input (HSC mode) at 100 kHz 32 bits |
Integrated connection type |
USB port with mini B USB 2.0 connector
Non isolated serial link serial 1 with terminal block connector and RS485 interface
Non isolated serial link serial 2 with terminal block connector and RS232/RS485 interface
Isolated serial link serial 2 with terminal block connector and RS485 interface |
Transmission rate |
1.2…115.2 kbit/s (115.2 kbit/s by default) for bus length of 15 m for RS485
1.2…115.2 kbit/s (115.2 kbit/s by default) for bus length of 3 m for RS232
12 Mbit/s for USB |
Communication port protocol |
USB port: USB – SoMachine-Network
Non isolated serial link: Modbus master/slave – RTU/ASCII or SoMachine-Network |
Local signalling |
1 LED (green) for PWR
1 LED (green) for RUN
1 LED (red) for module error (ERR)
1 LED (green) for SD card access (SD)
1 LED (red) for BAT
1 LED (green) for SL1
1 LED per channel (green) for I/O state |
Electrical connection |
Mini B USB 2.0 connectorfor a programming terminal
removable screw terminal blockfor inputs
removable screw terminal blockfor outputs
removable screw terminal block, 4 terminal(s) for connecting the serial link1
removable screw terminal block, 3 terminal(s) for connecting the 100-240 V AC power supply |
Maximum cable distance between devices |
Unshielded cable: <50 m for input
Shielded cable: <10 m for fast input
Shielded cable: <10 m for high speed input
Unshielded cable: <150 m for output |
Insulation |
Non-insulated between inputs
Between output and internal logic at 1780 V AC
Between output groups at 1780 V AC
Between supply and internal logic at 1780 V AC
Between input and internal logic at 500 V AC
Between fast input and internal logic at 500 V AC
Between input groups at 500 V AC |
Sensor power supply |
24 V DC at 250 mA supplied by the controller |
marking |
CE |
Mounting support |
Top hat type TH35-15 rail conforming to IEC 60715
Top hat type TH35-7.5 plate or panel with fixing kit conforming to IEC 60715 |
Height |
90 mm |
Depth |
70 mm |
Width |
110 mm |
Net weight |
0.359 kg |
Environment
IP degree of protection |
IP20 with protective cover in place |
product certifications |
CSA
cULus
IACS E10
RCM |
Standards |
IEC 61131-2
IEC 61010-2-201 |
Electromagnetic compatibility |
Electrostatic discharge immunity test – test level: 8 kV (air discharge) conforming to IEC 61000-4-2
Electrostatic discharge immunity test – test level: 6 kV (contact discharge) conforming to IEC 61000-4-2
Susceptibility to electromagnetic fields – test level: 10 V/m (80 MHz…3 GHz) conforming to IEC 61000-4-3
Magnetic field at power frequency – test level: 30 A/m conforming to IEC 61000-4-8
Electrical fast transient/burst immunity test – test level: 2 kV (power lines) conforming to IEC 61000-4-4
Electrical fast transient/burst immunity test – test level: 2 kV (relay output) conforming to IEC 61000-4-4
Electrical fast transient/burst immunity test – test level: 1 kV (I/O) conforming to IEC 61000-4-4
Electrical fast transient/burst immunity test – test level: 1 kV (serial link) conforming to IEC 61000-4-4
1.2/50 µs shock waves immunity test – test level: 1 kV (power lines (DC)) conforming to IEC 61000-4-5
1.2/50 µs shock waves immunity test – test level: 2 kV (power lines (AC)) conforming to IEC 61000-4-5
1.2/50 µs shock waves immunity test – test level: 2 kV (relay output) conforming to IEC 61000-4-5
1.2/50 µs shock waves immunity test – test level: 1 kV (I/O) conforming to IEC 61000-4-5
1.2/50 µs shock waves immunity test – test level: 1 kV (shielded cable) conforming to IEC 61000-4-5
1.2/50 µs shock waves immunity test – test level: 0.5 kV (power lines (DC)) conforming to IEC 61000-4-5
1.2/50 µs shock waves immunity test – test level: 1 kV (power lines (AC)) conforming to IEC 61000-4-5
Conducted RF disturbances – test level: 10 V (0.15…80 MHz) conforming to IEC 61000-4-6
Conducted emission – test level: 79 dBμV/m QP/66 dBμV/m AV (power lines (AC)) conforming to IEC 55011
Conducted emission – test level: 73 dBμV/m QP/60 dBμV/m AV (power lines (AC)) conforming to IEC 55011
Radiated emission – test level: 40 dBμV/m QP class A (10 m) conforming to IEC 55011
Radiated emission – test level: 47 dBμV/m QP class A (10 m) conforming to IEC 55011
1.2/50 µs shock waves immunity test – test level: 1 kV (relay output) conforming to IEC 61000-4-5 |
Shock resistance |
15 gn for 11 ms
30 gn for 6 ms |
Immunity to microbreaks |
10 ms |
Vibration resistance |
3.5 mm at 5…8.4 Hz on symmetrical rail
1 gn at 8.4…150 Hz on symmetrical rail
3.5 mm at 5…8.7 Hz on panel mounting
2 gn at 8.7…150 Hz on panel mounting |
Relative humidity |
10…95 %, without condensation (in operation)
10…95 %, without condensation (in storage) |
Ambient air temperature for operation |
0…55 °C (horizontal installation) |
Ambient air temperature for storage |
-25…70 °C |
Pollution degree |
<= 2 |
Operating altitude |
0…2000 m |
Storage altitude |
0…3000 m |
Packing Units
Unit Type of Package 1 |
PCE |
Number of Units in Package 1 |
1 |
Package 1 Height |
9.598 cm |
Package 1 Width |
12.326 cm |
Package 1 Length |
13.738 cm |
Package 1 Weight |
508 g |
Unit Type of Package 2 |
S03 |
Number of Units in Package 2 |
18 |
Package 2 Height |
30 cm |
Package 2 Width |
30 cm |
Package 2 Length |
40 cm |
Package 2 Weight |
9744 g |
Unit Type of Package 3 |
P12 |
Number of Units in Package 3 |
432 |
Package 3 Height |
95 cm |
Package 3 Width |
80 cm |
Package 3 Length |
120 cm |
Package 3 Weight |
242856 g |