Measuring principle
Capacitive Solid
-
Characteristic / Application
Compact rod probe with build-up compensation
easy start up -
Specialities
FDA-listed material
-
Supply / Communication
10,8 … 45V DC, DC-PNP 3-wire
20 … 253V AC, or
20 … 55V DC, Relay output -
Ambient temperature
-40 °C … 80 °C
(-40 °F … 176 °F) -
Process temperature
-40 °C … 120°C
(-40 °F … 248 °F) -
Process pressure / max. overpressure limit
-1 … 25 bar
(-14.5 … 360 psi) -
Main wetted parts
PPS = Polyphenylene sulphide
(glass fibre content approx. 40%) -
Process connection
R1″
NPT1″ -
Sensor length
140 mm (5.51″)
-
Communication
PNP transistor output
Relay output (potential-free
change-over contact / SPDT) -
Certificates / Approvals
ATEX, IEC, FM, CSA, NEPSI, EAC
-
Options
Aluminium Housing
-
Application limits
Solids, grain size max. 30 mm (1.2″),
DK min 1,6
Flexural strength 1400 N (at probe tip)
Field of application
Minicap FTC260 is a simple and cost-effective rod probe for point level detection in bulk solids, particularly suited to applications involving aggressive media and heavy build-up. It is designed for point level detection of light bulk solids, e.g. grain products, flour, milk powder, animal feed, cement, chalk or gypsum.
For point level detection of light bulk solids, with a grain size up to max. 30mm and a dielectric constant εr ≥ 1.6. Typical applications: Grain products, flour, milk powder, animal feed, cement, chalk or gypsum.
Process connection: Threads
Temperature: -40 to +80°C (-40 to +176°F)
Pressure: -1 to +25bar (-14.5 to +360psi)
Sensor length: 140mm (5.51″)
International explosion protection certificates, overfill prevention WHG
Benefits
Simple mounting and commissioning without calibrationMechanical safety, cost-efficiency and long operating life due to no wearing partsHigh operational safety and reliability due to active build-up compensation