Deltabar PMD75B – differential pressure transmitter

  • Measuring principle

    Differential pressure

  • Characteristic

    Differential pressure transmitter which detects process anomalies like plugged impulse lines.
    Intuitive and clear wizards for commissioning, proof tests and verification.

  • Supply voltage

    Ex d, Ex e, non-Ex:
    10.5…35V DC
    Ex i: 10.5…30V DC

  • Reference Accuracy

    Standard:
    up to 0.05 %
    Platinum:
    up to 0.035 %

  • Long term stability

    0.025 % of URL/ year
    0.05 % of URL/ 5 years
    0.10 % of URL/ 10 years

  • Process temperature

    -40°C…+110°C
    (-40°F…+230°F)

  • Ambient temperature

    -40°C…+85°C
    (-40°F…+185°F)

  • Measuring cell

    10 mbar…250 bar
    (0.15 psi…3750 psi)

  • Smallest calibratable span

    0.25 mbar (0.00375 psi)

  • Vacuum resistance

    25 mbar (0.0375 psi)

  • Max. Turn down

    100:1

  • Max. overpressure limit

    1600 bar (23,200 psi)

  • Process connection

    NPT1/4-18
    RC1/4″

  • Material process membrane

    316L, AlloyC,
    Tantal,
    Monel,
    Gold

  • Material gasket

    PTFE, FKM, EPDM, FFKM

  • Fill fluid

    Silicone oil,
    Inert oil

  • Material housing

    Aluminium, 316L

  • Communication

    4…20 mA HART
    PROFINET with Ethernet-APL
    Bluetooth® wireless
    technology and app (optional)

  • Certificates / Approvals

    ATEX, CSA, IECEx, JPN Ex, INMETRO, NEPSI, UK Ex

  • Safety approvals

    SIL

  • Design approvals

    EN10204-3.1,
    NACE MR0103,
    NACE MR0175

  • Drinking water approvals

    NSF, KTW

  • Specialities

    Heartbeat Technology,
    Bluetooth® Operation and maintenance SmartBlue App,
    LED Module,
    RFID TAG for easy identification,
    Plug and play functionalities,
    HistoROM

  • Measuring principle

    Differential pressure

  • Characteristic / Application

    Differential pressure transmitter which detects process anomalies like plugged impulse lines.
    Intuitive and clear wizards for commissioning, proof tests and verification.

  • Specialities

    Heartbeat Technology,
    Bluetooth® Operation and maintenance with SmartBlue App,
    LED Module,
    RFID TAG for easy identification,
    Plug and play functionalities
    HistoROM

  • Supply / Communication

    Ex d, Ex e, non-Ex:
    10.5…35V DC
    Ex i:
    10.5…30V DC

  • Accuracy

    Standard:
    up to 0.05 %
    Platinum:
    up to 0.035 %

  • Long term stability

    0.025 % of URL/ year
    0.05 % of URL/ 5 years
    0.10 % of URL/ 10 years

  • Ambient temperature

    -54°C…+85°C
    (-65°F…+185°F)

  • Process temperature

    -40°C…+110°C
    (-40°F…+230°F)

Spread the love

Contact Us

    Please prove you are human by selecting the heart.