Measuring principle
Differential pressure
-
Product headline
Digital transmitter with metallic measuring diaphragms
Compact size
Modular transmitter
Long-term stability -
Max. measurement error
0,1%
“PLATINUM” 0,075% -
Max. process pressure
10mbar…40bar
(0.15…580psi) -
Medium temperature range
Temperature gradient from pressure piping
-
Display/Operation
Option
-
Outputs
4…20mA HART
-
Digital communication
HART
-
Hazardous area approvals
ATEX, FM, CSA, IECEx, INMETRO, NEPSI, TIIS
-
Functional safety
SIL
-
Material certificates
NACE MR0103
NACE MR0175
EN10204-3.1
-
Measuring principle
Differential pressure
-
Characteristic
Digital transmitter with metallic measuring diaphragms
Compact size
Modular transmitter
Long-term stability -
Supply voltage
4…20 mA HART
11,5…45V DC (Non Ex):
Ex ia: 11,5…30V DC
PROFIBUS PA:
9…32 V DC (Non Ex)
FOUNDATION Fieldbus:
9…32 V DC (Non Ex) -
Reference Accuracy
Standard 0.1%
Platinum 0.075% -
Long term stability
0.05% of URL/ year
0.13% of URL/ 5 years
0.23% of URL/ 10 years -
Process temperature
-40°C…+85°C
(-40°F…+185°F) -
Ambient temperature
-40°C…+85°C
(-40°F…+185°F) -
Measuring cell
10 mbar…40 bar
(0.15…580 psi) -
Smallest calibratable span
10 mbar (0.15 psi)
-
Max. Turn down
20:1
-
Max. overpressure limit
on one side:
160 bar
(2300 psi) -
Process connection
1/4-18 NPT
-
Material process membrane
316L, AlloyC,
-
Material gasket
Viton, PTFE, EPDM, NBR
-
Fill fluid