FOCUS-1 is the first smart meter valve specifically developed for the process industry 4.0. This multifunctional smart flow control instrument – developed by FOCUS-ON, a SAMSON and KROHNE company – combines sensors, actuator and control functionality in one device. By measuring flow, pressure and temperature simultaneously and regulating its valve function independently, all specified set points for control tasks such as pressure, flow or even external control variables can be accurately and reliably achieved. This makes FOCUS-1 the ideal smart control unit for processes that need to be controlled autonomously. It is equally suitable for greenfield projects as well as a drop-in replacement of conventional valves in existing brownfield applications.
FOCUS-1 provides extensive diagnostics. In addition to many device diagnostics, the module features “smart cavitation control” which enables it to identify, monitor and alarm different kinds of cavitation caused in a pipeline. This allows operators to carry out predictive maintenance measures, allowing them to avoid increased stress and wear of valve and piping ahead of time as well as to prevent unplanned downtime. Given its redundant flow measurement, FOCUS-1 can also detect possible wear of the valve seat and thus leaks.
Due to its advanced algorithms, the smart meter valve can also create a “digital twin”. This allows modelling the measured data in such a way that device function and operation can be maintained even in the event of a sensor failure. With the help of the digital twin, plant operators implement redundancy and thus permanently increase the reliability, safety and availability of their plant.
The combination of sensors, valve and controller with extensive diagnostic features translates into less engineering effort, reduced sourcing and installation costs, a more simple and compact measuring set-up as well as more efficient life cycle management and maintenance. This simplifies processes, reduces system complexity and sustainably reduces capital expenditure (CAPEX) and operational expense (OPEX).
Specifications
Depending on selected device configuration
General information
| Product type | Smart process node |
| Product family name | FOCUS |
| Product positioning | For flow and decentralised process control |
| Measurement variables | Flow rate, Temperature, Pressure |
| Control element | Linear globe control valve with pneumatic actuator |
| Measurement principle | Flow: ultrasonic |
| Measured media | Liquids |
| Ambient temperature |
-25…+55°C / -13…+131°F |
| Nominal diameter / size | DN50, DN80, DN100 / 2″, 3″, 4 |
| Power supply (VAC) |
85…250 VAC |
| Power supply (VDC) |
18…32 VDC |
| Input signal (set point) | 4…20 mA |
Operating conditions
| Process pressure |
max. 36 barg / 522.1 psig |
| Process temperature | -40…+180°C / -40…+356°F |
Materials
| Measuring tube | Austenitic stainless steel (1.4404/316L) |
| Sensors |
Ultrasonic transducers for flow measurement: 1.4404 / 316 |
| Control element |
Valve body / Bonnet: 1.4408 / ASTM A351 Gr.CF8M |
| Process connection | Austenitic stainless steel (1.4404/316L) |
Process connections
| Flange connections | EN (1092-1): DN50, DN80, DN100 ASME (B 16.5): 2″, 3″, 4 |
Installation conditions
| Inlet run | 4D |
| Outlet run | 0D |
Approvals/Standards
| Certificates/Approvals Ex | ATEX, IECEx |
| NAMUR compliance | NE 107, NE 21, NE 43, NE 53, NE 80 |
Communication
| Analogue outputs | 4…20 mA |
| Digital outputs | HART®, PROFINET, Wi-Fi, Ethernet |
Accuracy
| Uncertainty (of set point) | ≤±0.5% |