RN22 active barrier, power supply, analog signal doubler

  • Measuring principle

    Active barrier

  • Measuring principle

    Active barrier

  • Function

    1-channel
    2-channel
    Signal doubler

  • Loop power supply

    17,5 V ±1 V bei 20 mA open circuit
    voltage: 24,5 V ±5 %

  • Power Supply

    24 V DC

  • Input

    0/4…20 mA / HART
    feeding/not feeding

  • Output

    0/4…20 mA / HART
    active/passive

  • Certificates

    ATEX II3G Ex tc IIIC Dc
    CSA C/US AIS, I/2/ABCD
    EAC [Ex ia Ga] IIC, [Ex ia Da] IIIC, Ex ec IIC Gc
    JPN [Ex ia Ga] IIC, [Ex ia Da] IIIC, Ex ec IIC Gc
    INMETRO [Ex ia Ga] IIC,[Ex ia Da] IIIC, Ex ec IIC Gc
    NEPSI [Ex ia Ga] IIC, [Ex ia Da] IIIC, Ex ec IIC Gc
    UK II3G Ex tc IIIC Dc
    UK II(1)G [Ex ia Ga] IIC, II(1)D [Ex ia Da] IIIC, II3G Ex ec IIC Gc
    ATEX IECEx II(1)G [Ex ia Ga] IIC, II(1)D [Ex ia Da] IIIC, II3G Ex ec IIC Gc
    UL C/US
    DNV

  • SIL

    SIL 2 SC 3

  • Operation

    HART

Field of application
The 1- or 2-channel RN22 active barrier powers analog instrument loops and safety instrumented systems up to SIL 2 (SC 3). The intrinsically safe, HART® transparent interface establishes a reliable link between field devices and process control. It interfaces with 2-/4-wire devices in hazardous areas and provides a second galvanically isolated signal output acc. to NAMUR NE 175. This opens a second channel for the process optimization domain without affecting the traditional automation system.

Single- or two-channel active barrier, power supply or signal doubler0/4 to 20 mA analog signal transmission (NAMUR NE 43) and galvanic isolationIntrinsic safety for operation in hazardous areas (Zone 2)Bidirectional HART® communication (transparent)2- and 4-wire capability for instruments in hazardous areas (Zones 0/20)Ambient temperature range: -40 … 60 °C (-40 … 140 °F)

Benefits
Intrinsically safe interface device suited for use in safety instrumented systems up to SIL 2 (SC 3) in accordance with IEC 61508 Quick and easy wiring with screw or push-in terminals or power supply via power rail T-connector Easy access to frontside HART® connection taps Compact housing: up to two channels on 12.5 mm (0.49 in) for efficient use of space in control cabinets