Vibronic Point level detection Nivotester FTL325N

  • Measuring principle

    Vibration Liquids

  • Characteristic / Application

    Switching unit NAMUR technology for rail mounting
    SIL2, according 61511
    Intrinsically safe

  • Supply / Communication

    NAMUR
    24V AC,DC / 230V AC

  • Ambient temperature

    Single installation:
    -20 °C … 60 °C
    (-4 °F … 140 °F)
    Rail mounting:
    -20 °C … 50 °C
    (-4 °F … 122 °F)

  • Communication

    1 Channel: 1 level SPDT + 1 alarm SPST
    3 Channel: 3 level SPDT + 1 alarm SPST

  • Certificates / Approvals

    ATEX, FM, CSA, IEC Ex, INMETRO, NEPSI, EAC

  • Safety approvals

    Overfill prevention WHG
    SIL

  • Measuring principle

    Vibration Solids

  • Characteristic / Application

    Switching unit NAMUR technology for rail mounting
    SIL2, according 61511
    Intrinsically safe

  • Supply / Communication

    NAMUR
    24V AC,DC / 230V AC

  • Ambient temperature

    Single installation:
    -20 °C … 60 °C
    (-4 °F … 140 °F)
    Rail mounting:
    -20 °C … 50 °C
    (-4 °F … 122 °F)

  • Communication

    1 Channel: 1 level SPDT + 1 alarm SPST
    3 Channel: 3 level SPDT + 1 alarm SPST

  • Certificates / Approvals

    ATEX, FM, CSA, IEC Ex, INMETRO NEPSI

  • Safety approvals

    Overfill prevention WHG
    SIL

Field of application
Nivotester FTL325N is a switching unit for point level detection in liquid tanks, also in hazardous explosion areas. Also suitable for overfill prevention in tanks with combustible or non-combustible liquids harmful to water. Two-point control and point level detection. The perfect fit for applications in safety related systems with requirements for functional safety up to SIL2 in accordance to IEC 61508 /IEC 61511 using Liquiphant with electronic insert FEL56 or FEL58.

Switching unit with NAMUR input for rail mounting or single installation.
Ambient temperature: -20 to +50°C (-4 to +122°F)
International explosion protection certificates, overfill prevention WHG, marine approvals

Benefits
Nivotester FTL325N for connecting one, two or three measuring cells (1-, 2- or 3-channel devices)Intrinsically safe signal circuits Ex ia for use of measuring sensor in explosion hazardous areasFunctional safety up to SIL2 through line monitoringDIN Rail housing for simple series installation on standard rails in switch cabinetSimple wiring using pluggable terminal blocksNAMUR interface to EN 50227 (DIN 19234; NAMUR) or IEC 60947-5-6 to connect NAMUR sensors or electronic inserts

Spread the love

Contact Us

    Please prove you are human by selecting the heart.